Precautions
1. Strictly follow the heating curve during operation.
2. Do not put into use when the pressure difference is unstable.
3. When shutting down, the hot oil circulation pump can only be stopped after the oil temperature drops below 80°C.
4. Ensure good circulation of thermal oil under high temperature conditions.
5. During normal operation, maintain a high liquid level in the expansion tank and a low liquid level in the storage tank.
6. The oil outlet temperature must not exceed the allowable working temperature of the thermal oil.
7. Do not flush the furnace with water during emergency shutdown.
8. Do not mix different types of thermal oil.
9. The vent of the storage tank should be connected to a safe area.
10. The initial heating rate must follow the heating curve.
11. Start the induced draft fan before starting the forced draft fan, and stop the forced draft fan before stopping the induced draft fan.
12. The boiler room should be equipped with electrical and oil fire-fighting equipment.